Publication 1734-UM008B-EN-P - August 2005

A-26 1734-POINT I/O Module/RSLogix5000 Controller Tag Reference

Stored Data Note:

To interpret values from -2,147,483,648 to -1, use this conversion
formula:

Stored Data Tag Value + 4,294,967,296 = Actual Stored Data Tag
Value.
Example: For a read value of -1,794,967,296:
-1,794,967,296 + 4,294,967,296 = 2,500,000,000 actual value

Input Data

Data Type

Default
Value

Valid Data Values

Present Data

DINT

0

0 to 16,777,215

Stored Data

DINT

0

-2,147,483,648 to
2,147,483,647
(0 - 4,294,967,295)

Status

Zero Frequency Detected

Stored Data Count_2
Stored Data Count_3

A Input Status
B Input Status
Z Input Status

Output Status_8 (Output 0)
Output Status_9 (Output 1)

Output Fault_10 (Output 0)
Output Fault_11 (Output 1)

Not Ready

EEPROM Fault

Program Fault
(incomplete / incorrect / conflict)

INT
BIT 1

BIT 2
BIT 3

BIT 4
BIT 5
BIT 6

BIT 8
BIT 9

BIT 10
BIT 11

BIT 13

BIT 14

BIT 15

0

0=No Fault
1=Fault Detected

Cycles thru 0, 1, 2, 3, 0,
Increments after update

0=Input A/B/Z is Off
1=Input A/B/Z is On

0=Output is Off
1=Output is On

0=No Fault
1=Open or Over Load

0=Module Ready
1=Module Initializing

0=No Fault
1=EEPROM data bad

0=No Fault
1=Bad Configuration
(See Program Fault Note on
the next page)