3-2 Plan to Use Your Adapter

When the 1734-ACNR adapter cannot support any more
connections, it does not open the connection and issues the
error 0x11a. RSLogix5000 reports the following error:

For example, if the NUT = 5 ms and the RPI = 10 ms, the adapter
can support:

• one rack connection with up to 39 discrete I/O modules, or
• 16 direct connections to analog or specialty modules, or
• one rack connection (15 discrete I/O modules) plus 10 direct

connections to analog modules

To avoid overloading the 1734-ACNR adapter and to avoid this
error, we recommend that the RPI be no less than 10
milliseconds for rack connections and 50 milliseconds for direct
connections. If you use more than 35 digital I/O modules with a
rack connection, use RPI = 20 milliseconds.

For additional information, refer to the URLs:

• www.ab.com/io/
• support.rockwellautomation.com/(select knowledgebase)