Rockwell Automation 1734-ACNR POINT I/O ControlNet Adapter User Manual User Manual

Page 79

Advertising
background image

Publication 1734-UM008B-EN-P - August 2005

1734-POINT I/O Module/RSLogix5000 Controller Tag Reference A-17

1734-IT2
2 Channel Thermocouple Input, Isol.

Configuration Data

Data Type

Default
Value

Valid Data Values

Temperature Mode Channel 0

SINT

1

0=mV/Custom Scale
1=°C
2=°F
3=°K
4=°R

Cold Junction Enable Channel 0

SINT

1

0=Disabled
1=Enabled

Cold Junction Offset Channel 0

INT

0

0 to 7,000
(0.00-70.00)

Low Engineering Channel 1

INT

0

-32,768 to 32,767

High Engineering Channel 1

INT

7,000

-32,768 to 32,767

Alarm Disable Channel 1

SINT

0

0=Alarms Enabled
1=Alarms Disabled

Limit Alarm Latch Channel 1

SINT

0

0=No Latching
1=Alarms Latch

Notch Filter Channel 1

SINT

1

0=50Hz
1=60Hz
2=100Hz
3=120Hz
4=200Hz
5=240Hz
6=300Hz
7=400Hz
8=480Hz

Sensor Type Channel 1

SINT

5

0=mV
1=B
2=C
3=E
4=J
5=K
6=N
7=R
8=S
9=T

Digital Filter Channel 1

INT

0

0 to 10,000 ms

Low Alarm Limit Channel 1

INT

-32,768

-32,768 to 32,767

High Alarm Limit Channel 1

INT

32,767

-32,768 to 32,767

Low Low Alarm Limit Channel 1

INT

-32,768

-32,768 to 32,767

High High Alarm Limit Channel 1

INT

32,767

-32,768 to 32,767