Logic controller cable charts, Runtime communication cables - to controller – Rockwell Automation 2711P PanelView Plus Terminal User Manual User Manual

Page 166

Advertising
background image

166

Publication 2711P-UM001J-EN-P - November 2009

Chapter 7 Terminal Connections

Logic Controller Cable
Charts

The charts provide a summary of terminal connections to controllers
and network interface modules.

Runtime Communication Cables - To Controller

PanelView Plus and PanelView Plus CE Terminals to SLC Controllers

Cables: PanelView Plus and PanelView Plus CE to SLC Controllers

Protocol

PanelView Plus Comm Port

SLC-500, 5/01, 5/02

CH1 RJ45

(DH-485)

SLC-5/03, 5/04, 5/05

CH0 (9-pin RS-232)

(DF1 or DH-485)

SLC 5/03

CH1 (RJ45)

(DH-485)

SLC 5/04

CH1 (DH+)

SLC 5/05

CH1 (ENET)

DF1
(any)

RS-232 (DF1) Port (9-pin)
PanelView Plus 400 to 1500
2711P-RN22C

N/A

2711-NC13 (5 m/16 ft)

2711-NC14 (10 m/32 ft)

2706-NC13 (3 m/10 ft)

N/A

N/A

N/A

DH-485
(any)

RS-232 (DH-485) Port (9-pin)
PanelView Plus 400 to 1500
2711P-RN22C

Use AIC+ Module

(1761-NET-AIC)

Connect to Port 1 or 2

2711-NC13 (5 m/16 ft)

2711-NC14 (10 m/32 ft)

2706-NC13 (3 m/10 ft)

Use AIC+ Module

(1761-NET-AIC)

Connect to Port 1 or 2

N/A

N/A

DH-485 Port
PanelView Plus 400 and 600
2711P-RN3

(2)

1747-C10 (2 m/6 ft)

1747-C11 (0.3 m/1 ft)

1747-C20 (6 m/20 ft)

Use AIC+ Module

(1761-NET-AIC)

Connect to Port 3

1747-C10 (2 m/6 ft)

1747-C11 (0.3 m/1 ft)

1747-C20 (6 m/20 ft)

N/A

N/A

DH-485 Port
PanelView Plus 700 to 1500
2711P-RN6, -RN6K

1761-CBL-AS03

(3 m/10 ft)

1761-CBL-AS09

(9 m/30 ft)

Use AIC+ Module

(1761-NET-AIC)

Connect to Port 3

1761-CBL-AS03

(3 m/10 ft)

1761-CBL-AS09

(9 m/30 ft)

N/A

N/A

ControlNet

ControlNet Port
PanelView Plus 400 and 600
2711P-RN15C
PanelView Plus 700 to 1500
2711P-RN15S, -RN15SK

N/A

1747-KFC15A or

1747-SCRNR/A Module with ControlNet Cable

DeviceNet

(1)

DeviceNet Port
PanelView Plus 400 and 600
2711P-RN10C
PanelView Plus 700 to 1500
2711P-RN10H

N/A

Use 1747-SDN Module

with DeviceNet Cable

EtherNet/IP

EtherNet/IP Port
PanelView Plus 400 to 1500
All except 2711P-xxx5xx

N/A

Use 1761-NET-ENI Module

with Ethernet Cable

N/A

N/A

1585J-M Type

Cable or

2711P-

CBL-EX04

(4 m/14 ft)

(3)

Remote I/O

(1)

Remote I/O Port
PanelView Plus 400 to 1500
2711P-RN1, 2711P-RN6

SLC 5/02 only

Use 1747-SN with

Shielded Twinaxial Cable

(1770-CD)

Use 1747-SN Module with Shielded Twinaxial Cable (1770-CD)

DH+

DH+ Port
PanelView Plus 400 and 600
2711P-RN8
PanelView Plus 700 to 1500
2711P-RN6, -RN6K

N/A

N/A

N/A

Shielded

Twinaxial

Cable

(1770-CD)

N/A

(1)

DeviceNet and Remote I/O communication modules are no longer available. Cable information is provided for reference only.

(2)

For CE compliance, use the 1761-NET-AIC or 1747-AIC module for cable lengths longer than 30 m (98 ft).

(3)

EtherNet/IP direct connection from the terminal to an SLC 5/05 controller requires an Ethernet switch or the 2711P-CBL-EX04 crossover cable.

Advertising