Ac power connections, Protective earth connection – Rockwell Automation 2711P PanelView Plus Terminal User Manual User Manual

Page 56

Advertising
background image

56

Publication 2711P-UM001J-EN-P - November 2009

Chapter 3 Power Connections

AC Power Connections

PanelView Plus devices with an integrated AC power supply have
these power ratings.

The input power terminal block supports these wire sizes.

Wire Specifications for AC Power Terminal Block

Protective Earth Connection

PanelView Plus devices with an AC power input have a protective
earth/ground terminal that you must connect to a low-impedance
earth/ground.

The protective earth/ground connection is on the power input
terminal block. The protective earth terminal requires a minimum wire
gauge.

Protective Earth Wire Specifications for AC Power

Terminal

Voltage Range

Frequency

V A

400 and 600

85…264V AC

47…63 Hz

60V A max

700 to 1500

85…264V AC

47…63 Hz

160V A max

Terminal

Wire Type

Dual-wire Gauge

(1)

Single-wire Gauge

Terminal Screw Torque

400 and 600

Stranded

or solid

Cu 90 °C (194 °F)

22…16 AWG

22…14 AWG

0.45…0.56 Nm (4…5 lb•in)

700 to 1500

22…16 AWG

22…14 AWG

0.56 Nm (5 lb•in)

(1)

Two-wire max. per terminal

ATTENTION

The protective earth connection is required for both electrical
safety and Electromagnetic Compliance (EMC) with the
European Union (EU) EMC directive for CE-mark conformance.

Terminal

PE Symbol

Wire Type

Wire Gauge

Terminal Screw Torque

400 and 600

Stranded

or solid

Cu 90 °C (194

°F)

14…12 AWG

0.45…0.56 Nm (4…5 lb•in)

700 to 1500

14…12 AWG

0.56 Nm (5 lb•in)