Terminal Connections Chapter 7

Minimum Requirements

The software and firmware must be installed on the development
computer and the PanelView Plus terminal to configure and
communicate with an Allen-Bradley controller on a ControlNet
network.

ControlNet Unscheduled Communication

ControlNet Scheduled Communications

Software/Firmware

PanelView Plus 700 to 1500

PanelView Plus 400 or 600

FactoryTalk View Studio

Version 3.10 or later

Version 4.0 or later

FactoryTalk View Machine Edition Runtime

Version 3.10 or later

Version 4.0 or later

ControlNet Module Firmware

2711P-RN15S, Series A, Rev A
(firmware version 2.07 or later)

(1)

2711P-RN15C, Series B, Rev A
or later

(1)

This applies to terminals that are ordered as pre-configured units with the ControlNet module.

Requirements

PanelView Plus 700 to 1500

PanelView Plus 400 or 600

FactoryTalk View Studio

Version 3.20 or later

Version 4.0 or later

FactoryTalk View Machine Edition Runtime Version 3.20.04 or later

Version 4.0 or later

RSNetWorx for ControlNet

Version 5.11 or later

Version 6.0 or later

RSLogix 5000

Version 13.0 or later

Version 15.0 or later

ControlNet Module Firmware

2711P-RN15S, Series A, Rev C
(firmware version 3.08 or later)

(1)

2711P-RN15C, Series B, Rev A
or later

(1)

This applies to terminals that are ordered as preconfigured units with the ControlNet module.

WARNING

The ControlNet Communications Module, cat. no.
2711P-RN15S, will not run with FactoryTalk View ME firmware
version 3.20.04 or earlier. All ControlNet Modules with version
3.07 firmware must be upgraded to version 3.08 or later;
otherwise, outputs may turn on an indeterminate state.