Upgrade Firmware Chapter 8

Ignore this error. It will be corrected during the upgrade. Press
OK to acknowledge error and wait for terminal to reset.

14. On touch or touch-screen terminals, you must calibrate the

touch screen by selecting pointers in all four corners of the
screen and pressing the middle of the screen when prompted.

Ignore the following message if it appears. It means FactoryTalk
View ME is being installed. Do not touch the two buttons that
appear with the message.
Machine edition may be corrupted. Do you want to download
firmware?

Communication settings are cleared when the terminal is
upgraded. If Ethernet communications is used, reconfigure the
Ethernet communication settings using the values recorded
when preparing the terminal.

15. Replace the .MER files that you backed up before starting the

upgrade or download the new .MER files to the terminal.

16. Load the .MER file and run the project.

TIP

If a USB mouse is available, you can acknowledge the
error by selecting OK.

TIP

You can configure your application to start automatically
on power cycle under Startup Options.