Chapter 3 Power Connections

Connect AC Power

Follow these steps to connect the terminal to AC power.

1. Verify that the terminal is not connected to a power source.

2. Secure the AC power wires to the terminal block.

Follow the markings on terminal blocks and terminal for proper
connections.

3. Secure the protective earth/ground wire to the marked position

of the power input terminal block.

4. On the 700 to 1500 devices, also secure the functional

earth/ground wire to the functional earth terminal screw on the
back of the display to ground bus.

5. Apply AC power to the terminal.

WARNING

Explosion Hazard - Do not disconnect equipment unless power
has been switched off and area is known to be nonhazardous.

Disconnect all power before installing or replacing components.
Failure to disconnect power may result in electrical shock or
damage to the terminal.

ATTENTION

Improper wiring of the power terminals may result in voltage at
the communication connector shells.

Do not apply power to the terminal until all wiring connections
have been made. Failure to do so may result in electrical shock.

L1

L2/Neutral

Protective Earth
to Ground Bus

GND

L1

L2/Neutral

Protective Earth
to Ground Bus

Functional Earth/Ground

to Ground Bus

700 to 1500 AC Terminals

400 and 600 AC Terminals