Load the .mer file and run the project – Rockwell Automation 2711P PanelView Plus Terminal User Manual User Manual

Page 197

Advertising
background image

Publication 2711P-UM001J-EN-P - November 2009

197

Upgrade Firmware Chapter 8

If other terminals exist on the same Ethernet network, the
following error may display:

Error registering name on network (may be duplicate). Change
in system Control Panel and try again.

Ignore this error. It will be corrected during the upgrade. Press
OK to acknowledge error and wait for terminal to reset.

3. On touch or touch-screen terminals, you must calibrate the

touch screen by selecting pointers in all four corners of the
screen and pressing the middle of the screen when prompted.

Ignore the following message if it appears. It means FactoryTalk
View ME is being installed. Do not touch the two buttons that
appear with this message.
Machine edition may be corrupted. Do you want to download
firmware?

4. Remove the card and press F8 or Exit to reset the terminal.

When the upgrade is complete, a dialog box appears requesting
you to remove the CompactFlash card from the card slot.

Communication settings are cleared when the terminal is
upgraded. If Ethernet communications is used, reconfigure the
Ethernet communication settings using the values recorded
when preparing the terminal.

5. Replace the .MER files that you backed up before starting the

upgrade or download a new .MER file to the terminal.

6. Load the .MER file and run the project.

TIP

If a USB mouse is available, you can acknowledge this
error by selecting OK.

TIP

You can configure your application to start automatically
on power cycle under Startup Options.

Advertising