Rockwell Automation 2711P PanelView Plus Terminal User Manual User Manual

Page 54

Advertising
background image

54

Publication 2711P-UM001J-EN-P - November 2009

Chapter 3 Power Connections

On most PanelView Plus DC terminals, the earth/ground terminal is
internally connected to the DC- terminal within the product.

The PanelView Plus terminals have isolated and nonisolated
communication ports. Refer to

Communication Port Isolation

on page

169

for details.

ATTENTION

Damage or malfunction can occur when a voltage potential
exists between two separate ground points. Make sure the
terminal does not serve as a conductive path between ground
points at different potentials.

IMPORTANT

For more information, refer to Wiring and Grounding Guidelines
for PanelView Plus Devices, publication

2711P-TD001

.

Advertising