Rockwell Automation 2711P PanelView Plus Terminal User Manual User Manual
Page 70
70
Publication 2711P-UM001J-EN-P - November 2009
Chapter 4 Configuration Mode
Serial Properties
Field
Description
Valid Values
Device
The serial device your terminal is connected 
to.
PLC_CH0
KF2
SLC_CH0
KF3
KFC
KFC15
AC_CH0
Error Check
Type of error checking used. Error checking is 
automatically configured if Use Auto Config 
is set to Yes.
BCC, CRC
Parity
Type of parity used. The parity is 
automatically configured if Use Auto Config 
is set to Yes.
None, Odd, Even
Stop Bits
Number of stop bits used.
1 or 2
Ack Timeout
Ack/Poll timeout value in ms.
20…60,000 ms
Max Retries
Maximum number of retries before the serial 
driver fails.
0…255
Station
Station number based on a specific device.
PLC_CH0 0…77 (octal)
KF2
0…77 (octal)
SLC_CH0 0…31
KF3
0…31
KFC
1…99
KFC15
1…99
AC_CH0
0…255
Baud Rate
Data rate at which serial driver 
communicates. The baud rate is 
automatically configured if Use Auto Config 
is set to Yes.
110
300
600
1200
4800
9600
19,200
38,400
115,200
Use Auto Config
Automatically or manually configures the 
baud rate, parity, and error checking 
parameters.
Yes (auto configure)
No (manual configure)
Com Port
Communication port used on the terminal.
1 (COM1)
2 (COM2)