Terminal Connections Chapter 7
Remote I/O Connections
Use the Belden 9463 twin axial or equivalent cable (cat. no. 1770-CD),
to connect a terminal to a Remote I/O scanner. The maximum cable
length (link distance) is determined by the baud rate.
•
2800 m (10,000 ft) for 57.6 Kbps
•
1400 m (5,000 ft) for 115.2 Kbps
•
700 m (2,500 ft) for 230.4 Kbps
publication
. The user manual for the I/O scanner module
also provides cabling information.
PanelView Plus 700 to 1500 Terminals
PanelView Plus 400 and 600 Terminals
•
82
Ω
terminating resistor for 230.4 Kbps
•
150
Ω
terminating resistor for 57.6 Kbps
and 115.2 Kbps
•
82
Ω
terminating resistor for 230.4 Kbps
•
150
Ω
terminating resistor for 57.6 Kbps
and 115.2 Kbps
Belden
To Controller
To Controller
Terminating Resistor
Terminating Resistor
Clear 1
Shield SH 2
Blue 3
Clear 3
Shield SH 2
Blue 1
Belden
Remote I/0 Port on Communication Module
Remote I/0 Port on Communication Module