Dh-485/dh+/remote i/o module – Rockwell Automation 2711P PanelView Plus Terminal User Manual User Manual

Page 176

Advertising
background image

176

Publication 2711P-UM001J-EN-P - November 2009

Chapter 7 Terminal Connections

DH-485/DH+/Remote I/O
Module

Terminals with a DH-485/DH+/Remote I/O communication module
support communication with these networks.

DH+ networks

DH-485 networks

Remote I/O networks

You can communicate with only one network at one time.

The 700 to 1500 terminals support all protocols on one module. The
400 and 600 terminals require a separate module for each protocol.
The DH+, DH-485, and Remote I/O connections are different between
the modules for the 400 and 600 and 700 to 1500 terminals.

Module Connections

IMPORTANT

See your controller documentation for appropriate controller
connections.

IMPORTANT

When using the DH-485 module, catalog number 2711P-RN3,
with PanelView Plus 400 and 600 terminals, the cable length
must not exceed 30 m (98 ft) to comply with CE requirements.
For longer cable lengths, use the 1761-NET-AIC or 1747-AIC
module.

Allen

Bradley

DH-485

1

2
3

4

5

6

3

2

1

DH+
RIO

Remote I/O

*

3. Clear
2. Shield/Drain
1. Blue

DH+

*

3. Blue
2. Shield/Drain
1. Clear

1. Earth/Ground
2. Shield/Drain
3. Signal Ground
4. Channel B
5. Channel A
6. Termination Resistance

Status LED Indicator

700 to 1500 Terminals

400 and 600 Terminals

DH-485 Comm Module

DH+ Comm Module

*

Remote I/O (Single Rack) Comm Module

*

Blue (line 1)

Clear (line 2)

Shield/Drain

Blue (line 2)

Clear (line 1)

Shield/Drain

Comm. Connector

Programming

Connector

1. Data_H
2. Data_L
3. +24V DC Enable
4. Power 1
5. TX Enable
6. Shield
7. Ground
8. Power 2

Pin 1

Pin 8

DH-485 Module is
electrically isolated
from Network.

Pin 8

1 2 3

1 2 3

* Use a Belden 9463 twin axial or equivalent cable,
cat. no. 1770-CD.