Publication 2711P-UM001J-EN-P - November 2009

Chapter 2 Installation

The terminals have a temperature code of T4 when operating in a 55
°C (131 °F) maximum ambient temperature. Do not install the
terminals in environments where atmospheric gases have ignition
temperatures less than 135 °C (275 °F).

USB Ports

The terminals contain universal serial bus (USB) ports that comply
with hazardous location environments. This section details the
field-wiring compliance requirements and is provided in accordance
with the National Electrical Code, article 500.

PanelView Plus 400, 600, and 700 to 1500 Terminals Control Drawing

Selected nonincendive field wiring apparatus must have nonincendive
circuit parameters conforming with Table 2.

Table 1 - PanelView Plus 400, 600, and 700 to 1500 USB Port Circuit Parameters

Display Size

V

oc

I

sc

C

a

L

a

Groups

A and B

Groups

C and D

Groups

A and B

Groups

C and D

400 and 600

Series A and B

5.25V DC 1.68 A

10 µF

10 µF

15 µH

15 µH

400 and 600

Series C or later

5.25V DC 1.68 A

10 µF

10 µF

3.5 µH

15 µH

700 to 1500

5.25V DC 1.68 A

10 µF

10 µF

15 µH

15 µH

Table 2 - Required Circuit Parameters for the USB Peripheral Device

V

max

V

oc

I

max

I

sc

C

i

+ C

cable

C

a

L

i

+ L

cable

L

a

USB

Peripheral

Device

Nonincendive Field
Wiring Apparatus

USB Port

Nonincendive Field Wiring

Associated Nonincendive Field Wiring Apparatus

PanelView Plus 400, 600, and 700 to 1500 Host Product