4 connecting the option to the vsm500 unit – Rockwell Automation VSM500 Integrated Drive/Motor DeviceNet Option Board User Manual

Page 16

Advertising
background image

2-2

VSM500 DeviceNet Option Board

2.4

Connecting the Option to the VSM500 Unit

Step 1. Verify that power has been removed from the VSM500 unit and network.

Step 2. Use static control precautions.

Step 3. Remove the cover on the VSM500 unit by loosening the four cover screws

(see figure 2.1). The display cable is designed to disconnect when the cover
is removed.

Step 4. Mount the DeviceNet option board. Tighten all screws to 2.6 Nm (23 in-lb.).

Use the washer in the location shown in figure 2.2 to ground the option
board.

Step 5. Connect the unit cable on the DeviceNet option board to connector P3 on the

VSM500 unit. Connector P3 is next to the control signal terminal block.

!

ATTENTION: A VSM500 Integrated Drive/Motor and DeviceNet network
may contain voltages that can cause injury or death. Remove power from
the VSM500 unit and network, and then verify that bus voltage has
discharged to a zero before working on them. Failure to observe these
precaution could result in severe bodily injury or loss of life.

ATTENTION: The option contains ESD (Electrostatic Discharge)
sensitive parts that can be damaged if you do not follow ESD control
procedures. Static control precautions are required when handling the
drive. If you are unfamiliar with static control procedures, refer to any
applicable ESD protection handbook. Failure to observe these
precaution could result in damage to equipment.

Figure 2.1 – Removing the Cover

Figure 2.2 – Mounting the DeviceNet Option Board

2.6 N-m

(23 in-lb)