10 setting the communications fault action – Rockwell Automation VSM500 Integrated Drive/Motor DeviceNet Option Board User Manual

Page 29

Advertising
background image

Configuring the VSM500 Unit and DeviceNet Option Board

3-9

3.10 Setting the Communications Fault Action

The communications fault action determines how the VSM500 unit and DeviceNet
option board respond when communications are disrupted (e.g., disconnected cable).
By default, the VSM500 unit is faulted and stopped. You can change this setting if your
application requires a different setting.

Step 1. In the Device Configuration - Enhanced Mode dialog box (see figure 3.8),

double-click parameter 109 [

DNET

FAULT

MODE

]. The Device Configuration -

Modify Boolean Parameter dialog box appears.

Step 2. Select the appropriate setting for your application, and then click Save to

Device.

Step 3. Click OK to close the dialog box.

!

ATTENTION: Parameter 109 [

DNET

FAULT

MODE

] determines the action

of the option and connected VSM500 unit if communications are
disrupted. By default, this parameter faults and stops the VSM500 unit.
You can set this parameter so that the VSM500 unit continues to run.
Precautions should be taken to ensure that the setting of this parameter
does not create a hazard of injury or equipment damage. Failure to
observe these precautions could result in bodily injury or damage to
equipment.

Figure 3.14 – Modifying the Fault Action Parameter

Setting

Description

Fault and Stop

The VSM500 unit is faulted and stopped.

Ignore

The disruption is ignored and the VSM500 unit continues to run.
If this setting us used, another method of stopping the drive must
be available (via the Function Loss terminal or the Stop terminal).