Rockwell Automation VSM500 Integrated Drive/Motor DeviceNet Option Board User Manual

Page 64

Advertising
background image

B-6

VSM500 DeviceNet Option Board

Object

Mapping

Name and Description

Access

Rule

1

Units/

Range

Factory

Default

Drive Program Parameters (continued)

49

0x0F-49-1

Analog Maximum
The percent of analog input used to represent parameter 31 [

MAXIMUM

FREQUENCY

]. If the maximum analog input equals maximum frequency, no

action is needed. If it is desired to adjust the analog input to equal
parameter 31 [

MAXIMUM

FREQUENCY

], use parameter 08 [

ANALOG

INPUT

] to

adjust the analog input to the desired level and then enter the value in
parameter 49.

Get/

Set

2

0.0% to
100.0%

100.0%

50

0x0F-50-1

Fault Reset
Resets the drive after a fault. This parameter is a command. It will be reset
to 0 = No Action after the command is completed.

0 = No Action
1 = Reset Fault

Get/

Set

2

0 to 1

0

51

0x0F-51-1

Preset Speed 1
Programmed value that sets the frequency that the drive outputs when this
preset is selected.

Get/
Set

0.0 Hz to
120.0 Hz

10.0 Hz

52

0x0F-52-1

Preset Speed 2
Programmed value that sets the frequency that the drive outputs when this
preset is selected.

Get/
Set

0.0 Hz to
120.0 Hz

20.0 Hz

53

0x0F-53-1

Preset Speed 3
Programmed value that sets the frequency that the drive outputs when this
preset is selected.

Get/
Set

0.0 Hz to
120.0 Hz

30.0 Hz

54

0x0F-54-1

Preset Speed 4
Programmed value that sets the frequency that the drive outputs when this
preset is selected.

Get/
Set

0.0 Hz to
120.0 Hz

40.0 Hz

55

0x0F-55-1

Preset Speed 5
Programmed value that sets the frequency that the drive outputs when this
preset is selected.

Get/
Set

0.0 Hz to
120.0 Hz

50.0 Hz

56

0x0F-56-1

Preset Speed 6
Programmed value that sets the frequency that the drive outputs when this
preset is selected.

Get/
Set

0.0 Hz to
120.0 Hz

60.0 Hz

57

0x0F-57-1

Preset Speed 7
Programmed value that sets the frequency that the drive outputs when this
preset is selected.

Get/
Set

0.0 Hz to
120.0 Hz

70.0 Hz

DeviceNet Parameters

101 0x0F-101-1 Switches MAC ID

The state of the node address DIP switches (1 - 6). This address may not
reflect the present address of the module if the baud rate DIP switches are
set to 3. In this case, parameter 103 [

NV

MAC

ID

] is used.

Get

0 to 63

63

102 0x0F-102-1 Switches Baud

The state of the baud rate DIP switches (7 - 8).
0 = 125K BPS
1 = 250K BPS
2 = 500K BPS
3 = Use nonvolatile parameters for node address and baud rate settings.

Get

0 to 3

0

1

Get = Read. Set = Write. Set access is allowed only if DIP switch 10 on the VSM500 Integrated drive/motor is set to On (figure 2.3).

2

The parameter can be set only when the drive is stopped.

3

The parameter can be set only then the VSM500 Integrated drive/motor does not have an active I/O connection.