Rockwell Automation VSM500 Integrated Drive/Motor DeviceNet Option Board User Manual

Page 18

Advertising
background image

2-4

VSM500 DeviceNet Option Board

Step 3. On the DeviceNet option board, set switches 6 through 1 to a unique

DeviceNet address between 0 and 63. The default switch setting is 63.

Step 4. On the DeviceNet option board, set switches 7 and 8 to select the data rate

at which the network is operating. The default switch setting is to use the
setting of parameter 104 [

NV

BAUD

RATE

].

Table 2.2 – DeviceNet Option Board Switch Settings (Switches 1-6)

Node

Address

1

Switch

6 ----> 1

Node

Address

1

Switch

6 ----> 1

Node

Address

1

Switch

6 ----> 1

Node

Address

1

Switch

6 ----> 1

0

000000

16

010000

32

100000

48

110000

1

000001

17

010001

33

100001

49

110001

2

000010

18

010010

34

100010

50

110010

3

000011

19

010011

35

100011

51

110011

4

000100

20

010100

36

100100

52

110100

5

000101

21

010101

37

100101

53

110101

6

000110

22

010110

38

100110

54

110110

7

000111

23

010111

39

100111

55

110111

8

001000

24

011000

40

101000

56

111000

9

001001

25

011001

41

101001

57

111001

10

001010

26

011010

42

101010

58

111010

11

001011

27

011011

43

101011

59

111011

12

001100

28

011100

44

101100

60

111100

13

001101

29

011101

45

101101

61

111101

14

001110

30

011110

46

101110

62

111110

15

001111

31

011111

47

101111

63

111111

1

If switches 7 and 8 are both On (1), then the DeviceNet option board uses the node address from parameter 103 [

NV

MAC

ID

]. The default

parameter setting is 63.

Table 2.3 – DeviceNet Option Board Switch Settings (Switches 7-8)

Data Rate

Switch 8

Switch 7

125 kBPS

0

0

250 kBPS

0

1

500 kBPS

1

0

Set by parameter 104 [

NV

BAUD

RATE

]

1

1

The default parameter setting is autobaud.

1

1