5 setting the node address – Rockwell Automation VSM500 Integrated Drive/Motor DeviceNet Option Board User Manual
Page 25

Configuring the VSM500 Unit and DeviceNet Option Board
3-5
Step 2. Double-click the icon for the VSM500 unit. The Device Configuration -
Enhanced Mode dialog box appears.
Parameters for the VSM500 unit and DeviceNet option board are displayed under
Parameters. You can either scroll through the parameters in the list, or you can select
a specific group of parameters in the Parameter Group box. Appendix B contains a
complete list of the parameters and parameter groups for the VSM500 unit and
DeviceNet option board.
3.5
Setting the Node Address
If switches 7 and 8 on the DeviceNet option board are On, the value of parameter 103
[
NV
MAC
ID
] determines the node address. By default, this parameter sets the node
address to 63. We recommend changing the node address to a new, unique node
address because all new devices use 63 as a default node address.
Step 1. In the Device Configuration - Enhanced Mode dialog box (see figure 3.8),
double-click parameter 103 [
NV
MAC
ID
]. The Device Configuration - Modify
Numeric Parameter dialog box appears.
Figure 3.8 – Device Configuration - Enhanced Mode Dialog Box
Figure 3.9 – Modifying the Node Address Parameter