Rockwell Automation VSM500 Integrated Drive/Motor DeviceNet Option Board User Manual
Page 79

DeviceNet Objects
C-11
Instance 2 Attributes: Polled I/O Connection
Attribute
ID
Access
Rule
Name
Data
Type
Value
1
Get
State
USINT
0 = Nonexistent
1 = Configuring
3 = Established
4 = Timed out
2
Get
Instance Type
USINT
1 = I/O Message
3
Get
Transport Class Trigger
USINT
0x83
4
Get
Produced Connection ID
UINT
01111xxxxxx
xxxxxx = Node Address
5
Get
Consumed Connection ID
UINT
10xxxxxx101
xxxxxx = Node Address
6
Get
Initial Comm. Characteristics
BYTE
0x01
7
Get
Produced Connection Size
UINT
0 to 4
8
Get
Consumed Connection Size
UINT
0 to 4
9
Get/Set
Expected Packet Rate
UINT
Timer Resolution of 2 msec
12
Get/Set
Watchdog Timeout Action
USINT
0 = Transition to time out
1 = Auto delete
2 = Auto reset
13
Get
Produced Connection Path
Length
UINT
6
14
Get
Produced Connection Path
0x20, 0x04, 0x24, XX, 0x30,
0x03
1
1
Refer to the DeviceNet specification for a description of the connection path
.
15
Get
Consumed Connection Path
Length
UINT
6
16
Get
Consumed Connection Path
0x20, 0x04, 0x24, XX, 0x30,
0x03
1