Rockwell Automation VSM500 Integrated Drive/Motor DeviceNet Option Board User Manual
Page 71
Advertising
DeviceNet Objects
C-3
Instance 2 Attributes: DeviceNet Option Instance
Common Services
Attribute
ID
Access Rule
Name
Data Type
Value
1
Get
Vendor ID
UINT
5
2
Get
Device Type
UINT
12
3
Get
Product Code
UINT
75
4
Get
Revision
Major Revision
Minor Revision
Structure of
USINT
USINT
1
7
5
Get
Status
WORD
Bit 0 = Owned
Bit 2 = Configured
Bit 10 = Recoverable Fault
Bit 11 = Unrecoverable Fault
6
Get
Serial Number
UDINT
Unique 32 bit number
7
Get
Product Name
String Length
ASCII String
Structure of
USINT
STRING
29
“VSM500 DeviceNet Interface”
Service Code
Implemented for
Service Name
Class
Instance
0x05
No
Yes
Reset
0x0E
Yes
Yes
Get_Attribute_Single
0x11
Yes
No
Find_Next_Object_Instance
Advertising