DeviceNet Objects

C-21

Common Services

13

Get

Fault Code

UINT

0x0000 = No fault
0x1000 = general fault
0x2220 = over current
0x3210 = high bus
0x3220 = low bus (stopped)
0x3221 = low bus (running)
0x4310 = drive overtemp
0x5300 = function loss
0x5301 = tb redundant start
0x6310 = eeprom parameter checksum
0x6311 = devicenet eeprom
0x6312 = eeprom drive id
0x7122 = thermal overload
0x7500 = no devicenet power
0x7501 = devicenet lost i/o connection
0x7502 = devicenet unrecoverable fault
0x7504 = devicenet forced fault
0x7505 = devicenet communication fault
0x7510 = communication loss
0x7700 = keypad disconnected
0x7701 = display fixed pattern
0x7702 = keypad redundant start
0x7703 = keypad connected

14

Get

Warn Code

UINT

0

15

Get

Ctrl From
Net

BOOL

0 = TB or keypad control
1 = Network control

16

Get/Set DNet Fault

Mode

USINT

0 = Fault and Stop
1 = Ignore

17

Get/Set Force

Fault/Trip

BOOL

0 -> 1 = Force fault

102

1

Get/Set DNet Preset

Command

USINT

0 to 7

103

1)

Get/Set DNet Speed

Ref RPM

UINT

0 to 3600 (RPM)

104

1

Get/Set DNet Speed

Ref Hz

UINT

0 to 120.0 (0.1 Hz)

Service Code

Implemented for

Service Name

Class

Instance

0x05

No

Yes

Reset

0x0E

Yes

Yes

Get_Attribute_Single

0x10

No

Yes

Set_Attribute_Single

Attribute

ID

Access

Rule

Name

Data

Type

Value

1

This attribute can be set only when the expected packet rate (EPR) for the explicit connection is

non-zero and the VSM500 unit does not have an active I/O connection.