Parameters

B-3

B.3 Parameter List

#

Object

Mapping

Name and Description

Access

Rule

1

Units/

Range

Factory

Default

Drive Display Parameters

01

0x0F-1-1

Command Frequency
Value of the presently selected speed reference.

Get

0.1 Hz

None

02

0x0F-2-1

Output Frequency
Output frequency to the motor.

Get

0.1 Hz

None

03

0x0F-3-1

Output Voltage
Output voltage to the motor.

Get

1 Volt

None

04

0x0F-4-1

Output Current
Output current to the motor.

Get

0.1% of
Rated
Current

None

05

0x0F-5-1

Load Current
Output current to the motor due to the load.

Get

0.1% of
Rated
Current

None

06

0x0F-6-1

Bus Voltage
DC Bus voltage level.

Get

1 Volt

None

07

0x0F-7-1

Power Unit Temperature
Temperature of the VSM500 unit.

Get

1 °C

None

08

0x0F-8-1

Analog Input
The value of the analog speed reference input (terminal 2 or 3 on the
control signal terminal block).

Get

0.1% of
Full
Scale

None

09

0x0F-9-1

TB Input Status
The on (1) and off (0) state of the inputs to the control signal terminal block:

Get

Bits

None

10

0x0F-10-1

Last Fault
Fault number for the most recent fault.
0 = No Fault
1 = Function Loss
2 = Over Current
3 = Motor Overload
4 = Over Voltage
5 = Under Voltage Stop
6 = Over Temperature
7 = Communication Loss
8 = Parameter Checksum
9 = EEPROM Drive ID

Refer to Chapter 7 for troubleshooting

10 = Keypad Disconnect
11 = Keypad Fixed Pattern
12 = Keypad Redundant Start
13 = TB Redundant Start
14 = Keypad Connect
15 = Under Voltage Running
20 = DNet EEPROM Fault
21 = DNet Unrecoverable Fault
22 = No DNet Power
23 = DNet Lost I/O Connection
24 = DNet Forced Fault
procedures.

Get

0 to 24

None

1

Get = Read. Set = Write. Set access is allowed only if DIP switch 10 on the VSM500 Integrated drive/motor is set to On (figure 2.3).

2

The parameter can be set only when the drive is stopped.

3

The parameter can be set only then the VSM500 Integrated drive/motor does not have an active I/O connection.

Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0

Bit 8

Bit 9

Bit 10

Bit 11

Bit 12

Bit 13

Bit 14

Bit 15

Stop

Start

Reset

Forward/Reverse

Function Loss

RPM/Percent Load

Not Used

Not Used

Speed Preset 0

Speed Preset 1

Speed Preset 2

Not Used