Rockwell Automation VSM500 Integrated Drive/Motor DeviceNet Option Board User Manual

Page 62

Advertising
background image

B-4

VSM500 DeviceNet Option Board

#

Object

Mapping

Name and Description

Access

Rule

1

Units/

Range

Factory

Default

Drive Program Parameters

30

0x0F-30-1

Minimum Frequency
Lowest frequency that the drive will output continuously. Its value must be
less that parameter 31 - [

MAXIMUM

FREQUENCY

].

Get/

Set

2

0 Hz to
60 Hz

0 Hz

31

0x0F-31-1

Maximum Frequency
Highest frequency that the drive will output. Its value must be greater that
the value of parameter 30 [

MINIMUM

FREQUENCY

].

Get/

Set

2

50 Hz to
120 Hz

60 Hz

32

0x0F-32-1

Accel Time
Time for the drive to ramp from 0 Hz to the value of parameter 31
[

MAXIMUM

FREQUENCY

]. The accel time is linear.

Get/
Set

1.0 Sec.
to 90.0
Sec.

5.0 Sec.

33

0x0F-33-1

Decel Time
Time for the drive to ramp from the value of parameter 31
[

MAXIMUM

FREQUENCY

] to 0 Hz. The decel ramp is linear.

Get/
Set

1.0 Sec.
to 90.0
Sec.

5.0 Sec.

34

0x0F-34-1

Start Source
Source of the start command.
0 = Keypad
1 = Terminal Block
2 = Network

Important:

The drive requires a stop input at the control terminal block,
regardless of the start source selection.

Get/

Set

2

0 to 2

0

35

0x0F-35-1

Run On Power Up
If enabled, output power is applied to the motor automatically at drive
power up.
0 = Disabled
1 = Enabled

Important:

This parametrer is ignored if parameter 34 [

START

SOURCE

] is

set to 2 = Network. The drive will start in network mode if the
network run command is set

.

Get/
Set

0 to 1

0

36

0x0F-36-1

Speed Reference Source
Source of the speed reference.
0 = Keypad/Preset Speeds
1 = Analog/Preset Speeds
2 = Network

Get/
Set

0 to 2

0

37

0x0F-37-1

Relay Control
Status indication provided by the normally open (N.O.) relay control output
(control terminals 19 and 20). Refer to the VSM500 Integrated Drive/Motor
User Manual information on these terminals.
0 = Running
1 = No Fault
2 = At Reference

Get/
Set

0 to 2

0

38

0x0F-38-1

Auto Restart Attempts
Maximum number of times that the drive will try to reset a fault.

Get/
Set

0 to 10

0

1

Get = Read. Set = Write. Set access is allowed only if DIP switch 10 on the VSM500 Integrated drive/motor is set to On (figure 2.3).

2

The parameter can be set only when the drive is stopped.

3

The parameter can be set only then the VSM500 Integrated drive/motor does not have an active I/O connection.

!

ATTENTION: When this feature is enabled, the drive may
start at any moment. This feature may only be used as
outlined in NFPA 79, Under Voltage Protection for
specialized applications. Failure to observe these
precautions could result in severe bodily injury or loss of
life.

Advertising