Rockwell Automation VSM500 Integrated Drive/Motor DeviceNet Option Board User Manual

Page 88

Advertising
background image

C-20

VSM500 DeviceNet Option Board

C.10 Class Code 0x29 – Control Supervisor Object

Class Attributes

Instance 1 Attributes

Attribute ID

Access Rule

Name

Data Type

Value

1

Get

Revision

UINT

1

2

Get

Max Instance

UINT

1

6

Get

Max ID Class

UINT

7

7

Get

Max ID Instance

UINT

17

Attribute

ID

Access

Rule

Name

Data

Type

Value

1

Get

Number of
Attributes

USINT

17

2

Get

Attributes
List

Array of
USINT

1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 16,
17

3

Get/Set

1

Run 1

BOOL

See Run/Stop Event Matrix on page C-22.

4

Get/

Set

1

Run 2

BOOL

See Run/Stop Event Matrix on page C-22.

5

Get/

Set

1

NetCtrl

BOOL

0 = TB or keypad control
1 = Network control

6

Get

State

USINT

3 = Ready
4 = Enabled
5 = Stopping
7 = Faulted

7

Get

Running 1

BOOL

0 = Not running forward
1 = Running forward

8

Get

Running 2

BOOL

0 = Not running reverse
1 = Running reverse

9

Get

Ready

BOOL

0 = Other state
1 = Ready or Enabled or Stopping

10

Get

Faulted

BOOL

0 = No faults present
1 = Fault occurred (latched)

11

Get

Warning

BOOL

0

12

Get/
Set

Fault Reset

BOOL

0 = No action
0 -> 1 = Fault Reset

1

This attribute can be set only when the expected packet rate (EPR) for the explicit connection is

non-zero and the VSM500 unit does not have an active I/O connection.