9 enabling network speed reference – Rockwell Automation VSM500 Integrated Drive/Motor DeviceNet Option Board User Manual

Page 28

Advertising
background image

3-8

VSM500 DeviceNet Option Board

Step 2. Select Network, and then click Save to Device.

Step 3. Click OK to close the dialog box.

3.9

Enabling Network Speed Reference

In order for a scanner to change the speed of the VSM500 unit, the unit must be
configured to accept its speed reference from the network.

Step 1. In the Device Configuration - Enhanced Mode dialog box (see figure 3.8),

double-click parameter 36 [

SPEED

REF

SOURCE

]. The Device Configuration -

Modify Enumerated Parameter dialog box appears.

Step 2. Select Network, and then click Save to Device.

Step 3. Click OK to close the dialog box.

Figure 3.12 – Modifying the Network Control Parameter

Figure 3.13 – Modifying the Speed Reference Parameter