7-4

VSM500 DeviceNet Option Board

9

0x6312

F.Id

EEPROM Drive
ID

Contents of the EEPROM
is corrupted.

- Reset parameters to default values and

cycle power.

- If fault persists, replace VSM500 unit.

10

0x7700

F.dcn

Keypad
Disconnect

Keypad cable
disconnected while
VSM500 unit under
power.

Remove power from the VSM500 unit.
Check keypad cable connection. Reapply
power to the VSM500 unit.

11

0x7701

F.ddP

Keypad Fixed
Pattern

Keypad cable connected
while VSM500 unit under
power.

Remove power from the VSM500 unit.
Check the keypad cable connection.
Reapply power to the VSM500 unit.

12

0x7702

F.dSF

Keypad
Redundant Start

Keypad hardware failure.

Remove power from the VSM500 unit.
Check the keypad cable connection.
Reapply power to the VSM500 unit.

13

0x5301

F.rSF

TB Redundant
Start

Regulator board failure.

Remove power from the VSM500 unit.
Check the keypad cable connection.
Reapply power to the VSM500 unit.

14

0x7703

F.drc

Keypad Connect Keypad cable connected

while VSM500 unit under
power.

Remove power from the VSM500 unit.
Check the keypad cable connection.
Reapply power to the VSM500 unit.

15

0x3221

F.LU

Under Voltage
while Running

Low input line or
temporary loss of input
line.

Check input line to verify voltage is within
operating specifications.

20

0x6311

F.dnE

DNet EEPROM
Fault

DeviceNet option board
EEPROM has invalid
data.

Use parameter 113 [

RESET

] to reset option

board parameters to factory defaults.

21

0x7502

F.dnU

DNet
Unrecoverable
Fault

No communication is
occurring. Fault occurs
when duplicate node
address exists or wrong
data rate is set.

Check DIP switch settings on the
DeviceNet option board for proper data
rate and node address. If DIP switches 7
and 8 on the DeviceNet option board are
both set to On, check parameter 103 [

NV

MAC

ID

] and parameter 104 [

NV

BAUD

RATE

]. Then reset the option board.

22

0x7500

F.dnP

No DNet Power 24 volt network power is

not detected.

Check DeviceNet connector at
Communication Module. Also, check
network’s power supply.

23

0x7501

F.dnL

DNet Lost I/O
Connection

Polled I/O connection
timed out.

Check DeviceNet master device for correct
operation (i.e., powered up, scanner online,
etc.).

24

0x7504

F.dnF

DNet Forced
Fault

Control Supervisor Object
(Class Code 0x29)
attribute 17 was set to 1.

Clear fault.

25

0x7505

F.dnC

DNet Comm
Fault

Communication failure
between DeviceNet
option board and unit.

Check the unit cable connecting the
DeviceNet option board and VSM500 unit.

1

Parameter fault codes are viewed in parameter 10 [

LAST

FAULT

]. DeviceNet fault codes are read from Class 0x29, Instance 1, Attribute 13.

Display fault codes are viewed on the LED display on the local operator control keypad.

Fault Codes