Troubleshooting

7-3

7.3

Fault Codes

When there is a fault, you can view the fault code using the value in parameter 10
[

LAST

FAULT

], the value of Class 0x29 (Control Supervisor Object), Instance 1,

Attribute 13 (Fault Code), or the display on the keypad.

Fault Codes

1

Name

Description

Corrective Action

Parameter

Value

DeviceNet Display

0

0x0000

No Fault

Normal operation.

No action required.

1

0x5300

F.FL

Function Loss

Open connection on
Function Loss control
terminal block inputs
(terminals 7 and 11).

- Check and restore the Function Loss

connection on the terminal block. Refer to
VSM500 Integrated Drive/Motor User
Manual.

- Check the external sensors wired into the

Function Loss string.

2

0x2220

F.OC

Over Current

Shaft rotation blocked.

Excessive driven load.

Input power is not
correctly wired to the
VSM500 unit.

Motor section ground
fault.

- Check for obstructions to shaft rotation.

- Reduce excessive load.
- Increase accel/decel time using the rotary

switches or parameter 32 [

ACCEL

TIME

]

and parameter 33 - [

DECEL

TIM

e].

- Verify that input wiring is correctly

connected. Refer to the VSM500
Integrated Drive/Motor User Manual.

- Check motor section for ground fault.

Replace VSM500 unit if a ground fault is
detected.

3

0x7122

F.OL

Motor Overload Excessive current to

motor for an extended
time due to excessive
load or short circuit.

- Check for obstruction to shaft rotation.
- Reduce the driven load.
- Check input wiring is correctly connected.

Refer to the VSM500 Integrated
Drive/Motor User Manual.

- Check for blower obstruction.
- Replace blower if required.

4

0x3210

F.HU

Over Voltage

High input line.

Deceleration time is too
fast or overhauling load.

- Check input line to verify that voltage is

within operating specification.

- Increase deceleration time using the

accel/decel rotary switch. Refer to the
VSM500 Integrated Drive/Motor User
Manual.

5

0x3220

F.LU

Under Voltage
while Stopped

Low input line or
temporary loss of input
line.

Check input line to verify voltage is within
operating specifications.

6

0x4310

F.OH

Over
Temperature

Operating environment is
too hot.

Blower is blocked or not
operating.

Excessive driven load.

- Check the application site and verify the

ambient temperature is within the
operating specification.

- Check for blower obstruction. Replace

blower if required.

- Reduce load or make sure VSM500 unit

matches the application requirement.

7

0x7510

F.CL

Communication
Loss

Communication between
the DeviceNet option
board and the drive has
failed.

Check cable connection between the
regulator board and DeviceNet option
board.

8

0x6310

F.dCH

Parameter
Checksum

Contents of the EEPROM
is corrupted.

Reset parameters to default values and
cycle power.

1

Parameter fault codes are viewed in parameter 10 [

LAST

FAULT

]. DeviceNet fault codes are read from Class 0x29, Instance 1, Attribute

13. Display fault codes are viewed on the LED display on the local operator control keypad.