Dell PowerEdge C6145 User Manual

Page 100

Advertising
background image

100

|

Using the System Setup Program


Table 2-2. The IPMI Command Table

IPMI Command

Setup Option

Description

ipmitool raw 0x34 0xB1
<Byte1:4>
Byte 1 - Power
Management Enable(01h
enable)
Byte 2 - Power Capping

Enable(01h enable)
Byte 3 - Current Chassis
Power Capping Value(Low
Byte)
Byte 4 - Current Chassis
Power Capping
Value(High Byte)

SET POWER
MANAGEMENT
BEHAVIOR

The setting controls PSU Power, its
range limited in 450˜2000 W. The
value is sent to BMC by IPMI
command and BMC will control
PSU power. This setting can be seen
when “Power Management” is

selected to “APML” mode and the
system board at location 2 in the
chassis.

ipmitool raw 0xc 1 1 3 <IP
Address>

IP Address

Use this option to input BMC LAN
port IP address.

ipmitool raw 0xc 1 1 6
<Subnet Mask>

Subnet Mask

Use this option to input BMC LAN
port subnet mask address.

ipmitool raw 0xc 1 1 12

<IP Address>

GateWay Address Use this option to input BMC LAN

port Gateway address.

ipmitool raw 0x30 1
Return: ID
ipmitool raw 0x30 3 ID
0x11 0x2 0 0 0 1 <Delay
Mode>

Power Staggering
AC Recovery

Configures power recovery behavior.
This item can be seen when
“Remote on AC Power Loss” is
selected in “Power On” or “Last
State”.
This parameter is only effective if
the Power Policy is not set to always
off.

0x00: Immediate Power On (No
Delay) : Default
0x01: Auto (Random), the auto

generated delay time must be in the
range of Minimum Power On Delay
and Maximum Power On Delay.
0x02: User Defined, the user

defined delay time must be in the
range of Minimum Power On Delay
and Maximum Power On Delay.

ipmitool raw 0x30 1

Minimum Power

Configures time for power on delay,