System 2
Solar system with 2 tanks and heat exchange
The controller calculates the temperature difference bet-
ween collector sensor S1 and tank sensor S2. If the diffe-
rence is larger than or identical to the adjusted switch-on
temperature difference, the pump (R1) will be switched on

and the tank will be loaded until the switch-off temperature
difference or the maximum tank temperature is reached.
Heat exchange between S3 and S4 is possible.

Relay

Description

R1

Solar pump

R2

Heat exchange pump

R3

optional:
Thermal disinfection
Booster pump
Parallel relay
Heat dump

R4

Sensor/Ter-
minal

Designation Description

S1

TCOL

Temperature collector

S2

TST1B

Temperature tank 1 bottom

S3

TST1T

Temperature tank 1 top

S4

TST2B

Temperature tank 2 top

S5

Optional sensor for measurement
purposes or options

VFS
RPS
V40

Adjustment channels

Channel

Sub channel 1

Sub channel 2 Factory

setting

Change to

Description

Page

ARR

1

2

System

78

LOAD >

Loading

DT O

12 °R

Switch-on temperature difference

78

DT F

8 °R

Switch-off temperature difference

78

DT S

20 °R

Set temperature difference

78

RIS

4 °R

Rise

78

S MAX

140 °F

Tank maximum limitation

79

SMAXS

2

Sensor tank max

79

COL >

Collector

CEM

270 °F

Collector emergency temperature

80

OCCO**

OFF

Option collector cooling

80

CMAX

230 °F

Maximum collector temperature

80

OCMI

OFF

Option collector minimum limitation

80

CMIN

50 °F

Minimum collector temperature

80

R4