Som 9s – STIEBEL ELTRON SOM 9s User Manual

Page 84

Advertising
background image

© Stiebel 11091_SOM_9s.mon

us.ind

d

| 84

SOM 9s

Time period - switch-on condition

LLOGI/ODB/tDTO

Time period - switch-on

condition

Adjustment range: 1 ... 100 s

in steps of 1 s

Factory setting: 60 s

The parameter tDTO is used for adjusting the time period

during which the switch-on condition DT O must be per-

manentely fulfilled.

Stabilization

LLOGI/ODB/tSTB

Stabilization

Adjustment range:

1.0 ... 15.0 min

in steps of 0.5 min

Factory setting: 2 min

The parameter tSTB is used for adjusting the time period

during which the switch-off condition DT F will be ignored

after the filling time has ended.

LLOGI/ODB/tFLL

Filling time

Adjustment range:

1.0 ... 30.0 min

in steps of 0.5 min

Factory setting: 5.0 min

The filling time can be adjusted using the parameter tFLL.

During this period, the pump runs at 100 % speed.

Filling time

By means of this function, tank loading continues after the

temperature difference between the collector and the tank

has fallen below the switch-off difference. Tank loading is

stopped if the adjusted

DT overrun difference between flow

and return sensor is underrun.

LLOGI/OOVRU

Selection: ON / OFF

Factory setting: OFF

Overrun

Booster function

LLOGI/ODB/OBST

Booster function

Adjustment range: ON / OFF

Factory setting: OFF

This function is used for switching on a second pump when

filling the solar system. When solar loading starts, R3/R4 is

energized in parallel to R1. After the filling time (tFLL) has

ended, R2 is switched off.

note:
The booster function is available in systems 1, 3,
8, 9, and 10 only.

Drainback option

A drainback system permits the heat transfer fluid to drain

back into the holding tank when solar energy is not coll-

ected. The drainback option will initiate the filling of the

system when solar loading begins. If the function is activated,

the menu items described in the following (tDTO, tFLL

and tSTB) have to be adjusted:

note:
The drainback option is only available in system

with one tank and one collector field and if no

cooling function is activated.

LLOGI / ODB

Drainback option

Selection: ON / OFF

Factory setting: OFF

note:
A drainback system requires additional com-

ponents such as a holding tank. The drainback

option should only be activated if all components

required are properly installed.

note:
If the drainback option ODB is activated, the

cooling functions and the antifreeze function will

not be available.

note:
If the drainback option ODB is activated, the

factory settings of the parameters DT O,

DT F and DT S will be adapted to values suiting

drainback systems. Additionally, the adjustment

range and the factory setting of the collector

emergency shutdown CeM will change.
Previous adjustments made in these channels

will be overridden and have to be entered again

if ODB is deactivated later on.