Tank set option

LLOGI / PRIO / OSTS

Tank set option
Selection ON / OFF
Factory setting: OFF

LLOGI / PRIO / TST1

Set temperature tank 1
Adjustment range: 38 ... 185 °F
Factory setting: 110 °F

Additionally, the following options can be activated:
Tank set option OSTS: If the selected priority tank

reaches its set temperature, the subordinate tank will be

loaded until it reaches its set temperature. After that, the

priority tank will be loaded up to its maximum tank tempe-

rature, then the subordinate tank. This function is available

in all 2-tank systems.

LLOGI / PRIO / TST2

Set temperature tank 2
Adjustment range: 38 ... 185 °F
Factory setting: 110 °F

Pause control

This function takes into account the actuation times of
valves and switches on the pump with a delay.
If the pause speed is activated, the relay of the tank which
has been loaded last remains switched on during the loading
break time. Speed is determined by the value adjusted in
nLO.
If the pump delay is activated, the corresponding relay for
the valve will be energized first. The pump(s) will be activa-
ted with the delay time (200s).

LLOGI / PSPEE

Pause speed
Selection: ON / OFF
Factory setting: OFF

LLOGI / PDELA

Pump delay
Selection: ON / OFF
Factory setting: OFF

LLOGI / PRIO / DTSE

Temperature diff. Spreaded
loading
Adjustment range: 40 ... 160 °R
Factory setting: 70 °R

Spreaded loading option
(for PRIO 1, 2, Su 1 or Su 2 only)

Spreaded loading option OSe: In 2-tank systems with 2
pumps, a spreaded loading function can be activated.
As soon as the adjustable spread difference DTSe between
the collector and the priority tank is reached, the second
tank will be loaded in parallel unless it is blocked. If the
temperature difference falls by 4 °R below DTSe, the pump
is switched off.
The collector temperature has to be higher than the tank
temperature.

LLOGI / PRIO / OSE

Spreaded loading option
Selection: ON / OFF
Factorsy setting: OFF

note:
In systems with pump logic, the parameter
PDeLA is not available.