SOM 9s

System 3
Solar system with 1 tank and backup heating
The controller calculates the temperature difference bet-
ween collector sensor S1 and tank sensor S2. If the diffe-
rence is larger than or identical to the adjusted switch-on
temperature difference, the pump (R1) will be switched on
and the tank will be loaded until the switch-off temperature
difference or the maximum tank temperature is reached.

Domestic hot water backup heating (R4) can be carried out
with a thermostat function (S3). If the value at S3 reaches
the switch-on temperature for the backup heating, the relay
is energized. If the value exceeds the switch-off temperature
for the backup heating, the relay is switched off again.

Sensor/Ter-
minal

Designation

Description

S1

TCOL

Temperature collector

S2

TSTB

Temperature tank bottom

S3

TSTT

Temperature tank top

S4

Optional sensor for measurement
purposes or options

S5

VFS
RPS
V40

Relay

Description

R1

Solar pump

R2

optional:
Thermal disinfection
Booster pump
Parallel relay
Heat dump

R3

R4

Backup heating/tank loading pump

Adjustment channels

Channel

Sub channel 1

Sub channel 2

Factory
setting

Change to

Description

Page

ARR

1

3

System

78

LOAD >

Loading

DT O

12 °R

Switch-on temperature difference

78

DT F

8 °R

Switch-off temperature difference

78

DT S

20 °R

Set temperature difference

78

RIS

4 °R

Rise

78

S MAX

140 °F

Tank maximum limitation

79

SMAXS

2

Sensor tank max

79

COL >

Collector

CEM

270 °F

Collector emergency temperature

80

OCCO**

OFF

Option collector cooling

80

R4

R1

S3

S2

S1

Temp. Sensor

Pt1000

L

R3

R2

R1

GND

S1

S2

S3

S4

S5

VBus

PW

M

1

PW

M

2

N

R4

V4

0

L'

VFS

RPS

out

in