Som 9s, 6 system layouts, R1 s2 s1 – STIEBEL ELTRON SOM 9s User Manual

Page 9

Advertising
background image

© Stiebel 11091_SOM_9s.mon

us.ind

d

9 |

SOM 9s

2.6

System layouts

System 1
Standard solar system with 1 tank
The controller calculates the temperature difference bet-
ween collector sensor S1 and tank sensor S2. If the diffe-
rence is larger than or identical to the adjusted switch-on

Relay

Description

R1

Solar pump

R2

optional:
Thermal disinfection
Booster pump
Parallel relay
Heat dump

R3

R4

Adjustment channels

Channel

Sub channel 1

Sub channel 2 Factory

setting

Change to

Description

Page

ARR

1

System

78

LOAD >

Loading

DT O

12 °R

Switch-on temperature difference

78

DT F

8 °R

Switch-off temperature difference

78

DT S

20 °R

Set temperature difference

78

RIS

4 °R

Rise

78

S MAX

140 °F

Tank maximum limitation

78

SMAXS

2

Sensor tank max

79

COL >

Collector

CEM

270 °F

Collector emergency temperature

80

OCCO**

OFF

Option collector cooling

80

CMAX

230 °F

Maximum collector temperature

80

OCMI

OFF

Option collector minimum limitation

80

CMIN

50 °F

Minimum collector temperature

80

Sensor/Ter-
minal

Designation Description

S1

TCOL

Temperature collector

S2

TSTB

Temperature tank bottom

S3

Optional sensor for measurement
purposes or options

S4

S5
VFS
RPS
V40

temperature difference, the pump (R1) will be switched on
and the tank will be loaded until the switch-off temperature
difference or the maximum tank temperature is reached.

R1

S2

S1

Temp. Sensor

Pt1000

L

R3

R2

R1

GND

S1

S2

S3

S4

S5

VBus

PWM

1

PWM

2

N

R4

V40

L'

VFS

RPS

out

in