The controller compares the temperature at sensor S1 to
the temperatures at sensors S2 and S3. If the measured
temperature differences are higher than the adjusted switch-
on temperature differences, the pump (R1) will be activated
and the corresponding tank zone will be loaded up to the
adjusted maximum temperature at most via the valve (R3).
The priority logic effects prior loading of the upper zone

of the tank.
With another temperature differential function (S3-heat
source/S4-heat sink) heating circuit return preheating (he-
ating circuit backup) is possible via another valve (R2). Do-
mestic hot water backup heating (R4) can be carried out
with a thermostat function (S3).

System 15
Solar system with vertical tank loading and backup heating via heating backup

R4

R3

R2

R1

S4

S3

S2

S1

Temp. Sensor

Pt1000

L

R3

R2

R1

GND

S1

S2

S3

S4

S5

VBus

PW

M

1

PW

M

2

N

R4

V4

0

L'

VFS

RPS

out

in

Adjustment channels

Channel

Sub channel 1

Sub channel 2 Factory

setting

Change to

Description

Page

ARR

1

15

System

78

LOAD1 >

Loading 1

DT1O

12 °R

Switch-on temperature difference 1

78

DT1F

8 °R

Switch-off temperature difference 1

78

DT1S

20 °R

Set temperature difference 1

78

RIS1

4 °R

Rise 1

78

S1MAX

140 °F

Tank maximum limitation 1

78

SMXS1

2

Sensor tank max 1

79

Sensor/Ter-
minal

Designation

Description

S1

TCOL

Temperature collector

S2

TSTB

Temperature tank bottom

S3

TSTT/TSTR Temperature tank top/

Temp. tank return preheating

S4

TRET

Temperature return

S5

Optional sensor for measurement
purposes or options

VFS
RPS
V40

Relay

Description

R1

Solar pump

R2

Return preheating

R3

3-port valve tank top/bottom

R4

Backup heating/tank loading pump

Note: 3-port valve normally open - tank bottom