SOM 9s

8

Messages

In the case of an error, the directional pad flashes red and a
message is indicated in the status display. A warning triangle
is additionally indicated. If more than one error or fault con-
dition has occurred, only the one with the highest priority
will be displayed as a message in the status display.

Error message

Value

Description

Solution

FS1...7
FS6, 8

-88.8

Short circuit at sensor 1...7

Check the cable

888.8

Broken cable at sensor 6, 8

EVFS

9999

Error at VFS sensor

Sensor fault. Check and, if necessary, cor-
rect the connection of the sensor plugs. If
a sensor signal does not appear, the sensor
has to be replaced

ERPS

9999

Error at RPS sensor

ELEAK

Measured minimum
pressure

Leakage error

Check the system for a leakage

EPRES

Measured maximum
pressure

Error pressure

Check the functioning of the valves and
pumps

EFLOW

Error flow rate
Threshold values for VFS 1-10: 1,0-1,1 l/min
Threshold values for VFS 2-40: 2,0-2,1 l/min

Check the pump
Check whether a flow rate exists

PARAM

Remote parametrization

Do not parametrize the controller via the
push buttons during remote parametriza-
tion

In the case of a sensor error, the system is switched off, and
a message appears on the display marked by an “E”. Addi-
tionally, a corresponding value for the error type assumed
is indicated.
After the error has been removed, the error message dis-
appears.