The controller compares the temperature at sensor S1 to
the temperatures at sensors S2 and S4. If the measured
temperature differences are higher than the adjusted switch-
on temperature differences, the pump (R1 and R2) will be
activated and the corresponding tank will be loaded up to

the adjusted maximum temperature. Tank 1 is loaded with
priority.
Heat exchange from tank 1 to tank 2 (R3) is possible with
another temperature differential function (S3-heat source/
S4-heat sink).

Adjustment channels

Channel

Sub channel 1

Sub channel 2 Factory

setting

Change to

Description

Page

ARR

1

17

System

78

LOAD1 >

Loading 1

DT1O

12 °R

Switch-on temperature difference 1

78

DT1F

8 °R

Switch-off temperature difference 1

78

DT1S

20 °R

Set temperature difference 1

78

RIS1

4 °R

Rise 1

78

S1MAX

140 °F

Tank maximum limitation 1

78

SMXS1

2

Sensor tank max 1

79

LOAD2 >

Loading 2

DT2O

12 °R

Switch-on temperature difference 2

78

DT2F

8 °R

Switch-off temperature difference 2

78

DT2S

20 °R

Set temperature difference 2

78

Sensor/Ter-
minal

Designation

Description

S1

TCOL

Temperature collector

S2

TST1B

Temperature tank 1 bottom

S3

TSTT

Temperature tank 1 top

S4

TST2B

Temperature tank 2 bottom

S5

Optional sensor for measurement
purposes or options

VFS
RPS
V40

Relay

Description

R1

Solar pump tank 1

R2

Solar pump tank 2

R3

Heat exchange pump

R4

optional:
Thermal disinfection
Parallel relay
Heat dump

System 17
2-tank solar system with pump logic and heat exchange control

R3

R2

R1

S4

S3

S2

S1

Temp. Sensor

Pt1000

L

R3

R2

R1

GND

S1

S2

S3

S4

S5

VBus

PW

M

1

PW

M

2

N

R4

V4

0

L'

VFS

RPS

out

in