Som 9s – STIEBEL ELTRON SOM 9s User Manual

Page 19

Advertising
background image

© Stiebel 11091_SOM_9s.mon

us.ind

d

19 |

SOM 9s

System 6
2-tank solar system with pump logic
The controller compares the temperature at sensor S1 to
the temperatures at sensors S2 and S4. If the measured
temperature differences are higher than the adjusted switch-
on temperature differences, the pump (R1 and R2) will be

activated and the corresponding tank will be loaded up to
the adjusted maximum temperature at most.

Sensor/Ter-
minal

Designation

Description

S1

TCOL

Temperature collector

S2

TST1B

Temperature tank 1 bottom

S3

Optional sensor for measurement
purposes or options

S4

TST2B

Temperature tank 2 bottom

S5

Optional sensor for measurement
purposes or options

VFS
RPS
V40

Relay

Description

R1

Solar pump tank 1

R2

Solar pump tank 2

R3

optional:
Thermal disinfection
Parallel relay
Heat dump

R4

Adjustment channels

Channel

Sub channel 1

Sub channel 2 Factory

setting

Change to

Description

Page

ARR

1

6

System

78

LOAD1 >

Loading 1

DT1O

12 °R

Switch-on temperature difference 1

78

DT1F

8 °R

Switch-off temperature difference 1

78

DT1S

20 °R

Set temperature difference 1

78

RIS1

4 °R

Rise 1

78

S1MAX

140 °F

Tank maximum limitation 1

78

SMXS1

2

Sensor tank max 1

79

LOAD2 >

Loading 2

DT2O

12 °R

Switch-on temperature difference 2

78

DT2F

8 °R

Switch-off temperature difference 2

78

DT2S

20 °R

Set temperature difference 2

78

RIS2

4 °R

Rise 2

78

R2

R1

S4

S2

S1

Temp. Sensor

Pt1000

L

R3

R2

R1

GND

S1

S2

S3

S4

S5

VBus

PWM

1

PWM

2

N

R4

V40

L'

VFS

RPS