The controller compares the temperatures at the collector
sensors S1 and S5 to the temperatures at S2 and S4. If one
of the measured temperature differences is higher than the
adjusted switch-on temperature differences, the correspon-

ding pump (R1, R2) or both pumps will be activated and
the corresponding tank will be loaded up to the adjusted
maximum temperature via the valve (R3).

Adjustment channels

Channel

Sub channel 1

Sub channel 2 Factory

setting

Change to

Description

Page

ARR

1

23

System

78

LOAD1 >

Loading 1

DT1O

12 °R

Switch-on temperature difference 1

78

DT1F

8 °R

Switch-off temperature difference 1

78

DT1S

20 °R

Set temperature difference 1

78

RIS1

4 °R

Rise 1

78

S1MAX

140 °F

Tank maximum limitation 1

78

SMXS1

2

Sensor tank max 1

79

LOAD2 >

Loading 2

DT2O

12 °R

Switch-on temperature difference 2

78

DT2F

8 °R

Switch-off temperature difference 2

78

DT2S

20 °R

Set temperature difference 2

78

Sensor/Ter-
minal

Designation

Description

S1

TCOL1

Temperature collector 1

S2

TST1B

Temperature tank 1 bottom

S3

Optional sensor for measurement
purposes or options

S4

TST2B

Temperature tank 2 bottom

S5

TCOL2

Temperature collector 2

VFS

Optional sensor for measurement
purposes or options

RPS
V40

Relay

Description

R1

Solar pump collector 1

R2

Solar pump collector 2

R3

3-port valve tank 1 / 2

R4

optional:
Thermal disinfection
Parallel relay
Heat dump

System 23
Solar system with east-/west collectors and 2 tanks (valve logic)

R3

R2

R1

S5

S4

S2

S1

Temp. Sensor

Pt1000

L

R3

R2

R1

GND

S1

S2

S3

S4

S5

VBus

PWM

1

PWM

2

N

R4

V40

L'

VFS

RPS

out

in

Note: 3-port valve normally open
- tank 1 (S2)