The controller calculates the temperature difference bet-
ween collector sensor S1 and tank sensor S2. If the diffe-
rence is larger than or identical to the adjusted switch-on
temperature difference, the pump (R1) will be switched on
and the tank will be loaded until the switch-off temperature

difference or the maximum tank temperature is reached.
With another temperature differential function (S3/S4)
heating circuit backup (heating circuit return preheating) is
possible via a valve (R2). With a thermostat function (S3)
domestic hot water backup heating (R4) can be carried out.

Sensor/Ter-
minal

Designation

Description

S1

TCOL

Temperature collector

S2

TSTB

Temperature tank bottom

S3

TSTT/TSTR Temperature tank top/

Temp. tank return preheating

S4

TRET

Temperature - return

S5

Optional sensor for measurement
purposes or options

VFS
RPS
V40

Relay

Description

R1

Solar pump

R2

Return preheating

R3

optional:
Thermal disinfection
Booster pump
Parallel relay
Heat dump

R4

Backup heating/tank loading pump

Adjustment channels

Channel

Sub channel 1

Sub channel 2 Factory

setting

Change to

Description

Page

ARR

1

10

System

78

LOAD >

Loading

DT O

12 °R

Switch-on temperature difference

78

DT F

8 °R

Switch-off temperature difference

78

DT S

20 °R

Set temperature difference

78

RIS

4 °R

Rise

78

S MAX

140 °F

Tank maximum limitation

78

SMAXS

2

Sensor tank max

79

COL >

Collector

CEM

270 °F

Collector emergency temperature

80

OCCO**

OFF

Option collector cooling

80

System 10
Solar system with 1 tank, heating circuit return preheating and thermostatic backup heating

R4

R2

R1

S4

S3

S2

S1

Temp. Sensor

Pt1000

L

R3

R2

R1

GND

S1

S2

S3

S4

S5

VBus

PWM

1

PWM

2

N

R4

V40

L'

VFS

RPS

out

in