Som 9s – STIEBEL ELTRON SOM 9s User Manual

Page 25

Advertising
background image

© Stiebel 11091_SOM_9s.mon

us.ind

d

25 |

SOM 9s

The controller calculates the temperature difference bet-
ween collector sensor S1 and tank sensor S2. If the diffe-
rence is larger than or identical to the adjusted switch-on
temperature difference, the pump (R1) will be switched on
and the tank will be loaded until the switch-off temperature

difference or the maximum tank temperature is reached.
With another temperature differential function (S3/S4)
heating circuit return preheating (heating circuit backup) is
possible via a valve (R2).

Sensor/Ter-
minal

Designation

Description

S1

TCOL

Temperature collector

S2

TSTB

Temperature tank bottom

S3

TSTR

Temp. tank return preheating

S4

TRET

Temperature - return

S5

Optional sensor for measurement
purposes or options

VFS
RPS
V40

Relay

Description

R1

Solar pump

R2

Return preheating

R3

optional:
Thermal disinfection
Booster pump
Parallel relay
Heat dump

R4

Adjustment channels

Channel

Sub channel 1

Sub channel 2 Factory

setting

Change to

Description

Page

ARR

1

9

System

78

LOAD >

Loading

DT O

12 °R

Switch-on temperature difference

78

DT F

8 °R

Switch-off temperature difference

78

DT S

20 °R

Set temperature difference

78

RIS

4 °R

Rise

78

S MAX

140 °F

Tank maximum limitation

78

SMAXS

2

Sensor tank max

79

COL >

Collector

CEM

270 °F

Collector emergency temperature

80

OCCO**

OFF

Option collector cooling

80

CMAX

230 °F

Maximum collector temperature

80

OCMI

OFF

Option collector minimum limitation

80

System 9
Solar system with 1 tank and heating circuit return preheating

R2

R1

S4

S3

S2

S1

Temp. Sensor

Pt1000

L

R3

R2

R1

GND

S1

S2

S3

S4

S5

VBus

PW

M

1

PW

M

2

N

R4

V4

0

L'

VFS

RPS

out

in