Som 9s – STIEBEL ELTRON SOM 9s User Manual

Page 45

Advertising
background image

© Stiebel 11091_SOM_9s.mon

us.ind

d

45 |

SOM 9s

The controller compares the temperatures at the coll-
ector sensors S1 and S5 to the tank temperature at
sensor S2. If one of the measured temperature diffe-
rences is higher than the adjusted switch-on tempera-
ture differences, the corresponding pump (R1, R2) or

both pumps will be activated and the tank will be loaded.
Heat transfer control to an existent tank (R3) can be carried
out with another temperature differential function (S3-heat
source/S4-heat sink).

Adjustment channels

Channel

Sub channel 1

Sub channel 2 Factory

setting

Change to

Description

Page

ARR

1

18

System

78

LOAD >

Loading

DT O

12 °R

Switch-on temperature difference

78

DT F

8 °R

Switch-off temperature difference

78

DT S

20 °R

Set temperature difference

78

RIS

4 °R

Rise

78

S MAX

140 °F

Tank maximum limitation

78

SMAXS

2

Sensor tank max

79

COL 1 >

Collector 1

CEM1

270 °F

Collector emergency temperature 1

80

OCCO1**

OFF

Option collector cooling 1

80

CMAX1

230 °F

Maximum collector temperature 1

80

OCMI1

OFF

Option collector minimum limitation 1

80

Sensor/Ter-
minal

Designation

Description

S1

TCOL1

Temperature collector 1

S2

TST1B

Temperature tank 1 bottom

S3

TSTT

Temperature tank 1 top

S4

TST2B

Temperature tank 2 bottom

S5

TCOL2

Temperature collector 2

VFS

Optional sensor for measurement
purposes or options

RPS
V40

Relay

Description

R1

Solar pump collector 1

R2

Solar pump collector 2

R3

Heat exchange pump

R4

optional:
Thermal disinfection
Parallel relay
Heat dump

System 18
Solar system with east-/west collectors and heat exchange control

R3

R2

R1

S5

S4

S3

S2

S1

Temp. Sensor

Pt1000

L

R3

R2

R1

GND

S1

S2

S3

S4

S5

VBus

PWM

1

PWM

2

N

R4

V40

L'

VFS

RPS

out

in