The controller compares the temperatures at the collector
sensors S1 and S5 to the tank temperature at sensor S2. If
one of the measured temperature differences is higher than
the adjusted switch-on temperature differences, the corre-

sponding pump (R1, R2) or both pumps will be activated and
the tank will be loaded. Domestic hot water backup heating
(R4) can be carried out with a thermostat function (S3).

Adjustment channels

Channel

Sub channel 1

Sub channel 2 Factory

setting

Change to

Description

Page

ARR

1

19

System

78

LOAD >

Loading

DT O

12 °R

Switch-on temperature difference

78

DT F

8 °R

Switch-off temperature difference

78

DT S

20 °R

Set temperature difference

78

RIS

4 °R

Rise

78

S MAX

140 °F

Tank maximum limitation

78

SMAXS

2

Sensor tank max

79

COL 1 >

Collector 1

CEM1

270 °F

Collector emergency temperature 1

80

OCCO1**

OFF

Option collector cooling 1

80

CMAX1

230 °F

Maximum collector temperature 1

80

OCMI1

OFF

Option collector minimum limitation 1

80

Sensor/Ter-
minal

Designation

Description

S1

TCOL1

Temperature collector 1

S2

TSTB

Temperature tank bottom

S3

TSTT

Temperature tank top

S4

Optional sensor for measurement
purposes or options

S5

TCOL2

Temperature collector 2

VFS

Optional sensor for measurement
purposes or options

RPS
V40

Relay

Description

R1

Solar pump collector 1

R2

Solar pump collector 2

R3

optional:
Thermal disinfection
Parallel relay
Heat dump

R4

Backup heating/tank loading pump

System 19
Solar system with east-/west collectors and thermostatic backup heating

R4

R2

R1

S5

S3

S2

S1

Temp. Sensor

Pt1000

L

R3

R2

R1

GND

S1

S2

S3

S4

S5

VBus

PW

M

1

PW

M

2

N

R4

V4

0

L'

VFS

RPS

out

in