Som 9s, 9troubleshooting – STIEBEL ELTRON SOM 9s User Manual

Page 98

Advertising
background image

© Stiebel 11091_SOM_9s.mon

us.ind

d

| 98

SOM 9s

9

Troubleshooting

If a malfunction occurs, a message will appear on the
display of the controller.

The display is permanently off.

Press button

5

. Display illuminated?

no

Check the power supply of the controller. Is it discon-
nected?

The fuse of the controller
could be blown. The fuse
holder (which holds the
spare fuse) becomes ac-
cessible when the cover
is removed. The fuse can
then be replaced.

Directional pad flashes red. The symbol

is indicates

on the display and the symbol

flashes.

Sensor fault An error code instead of
a temperature is shown on the sensor
display channel.

- 88.8

888.8

Cable is broken
Check the cable.

S h o r t c i r c u i t .
Check the cable.

Disconnected PT1000 temperature sen-
sors can be checked with an ohmmeter.
Please check the resistance values corre-
spond with the table.

The controller is protected by a fuse. The fuse holder (which
also holds the spare fuse) becomes accessible when the
cover is removed. To replace the fuse, pull the fuse holder
from the bottom.

Controller has been in
standby, everything o.k.

Check the supply line and
reconnect it.

yes

yes

fuse

WARnIng!

electric shock!
Upon opening the housing, live parts
are exposed.

Î

Always disconnect the control-
ler from power supply before
opening the housing!

°F

Ω

°F

Ω

14

961

131 1213

23

980

140 1232

32

1000

149 1252

41

1019

158 1271

50

1039

167 1290

59

1058

176 1309

68

1078

185 1328

77

1097

194 1347

86

1117

203 1366

95

1136

212 1385

104 1155

221 1404

113 1175

230 1423

122 1194

239 1442

resistance of the

Pt1000 sensors

no