The controller compares the temperature at sensor S1 to
the temperatures at sensors S2 and S4. If the measured tem-
perature differences are higher than the adjusted switch-on
temperature differences, the pump (R1) will be activated and

the corresponding tank will be loaded up to the adjusted
maximum temperature via the valve (R3). Tank 1 is loaded
with priority.

Sensor/Ter-
minal

Designation

Description

S1

TCOL

Temperature collector

S2

TST1B

Temperature tank 1 bottom

S3

Optional sensor for measurement
purposes or options

S4

TST2B

Temperature tank 2 bottom

S5

Optional sensor for measurement
purposes or options

VFS
RPS
V40

Relay

Description

R1

Solar pump

R2/R4

optional:
Thermal disinfection
Parallel relay
Heat dump

R3

3-port valve tank 1 / 2

Adjustment channels

Channel

Sub channel 1

Sub channel 2 Factory

setting

Change to

Description

Page

ARR

1

5

System

78

LOAD1 >

Loading 1

DT1O

12 °R

Switch-on temperature difference 1

78

DT1F

8 °R

Switch-off temperature difference 1

78

DT1S

20 °R

Set temperature difference 1

78

RIS1

4 °R

Rise 1

78

S1MAX

140 °F

Tank maximum limitation 1

78

SMXS1

2

Sensor tank max 1

79

LOAD2 >

Loading 2

DT2O

12 °R

Switch-on temperature difference 2

78

DT2F

8 °R

Switch-off temperature difference 2

78

System 5
2-tank system with valve logic, 1 pump, 3 sensors and 3-port valve

R3

R1

S4

S2

S1

Temp. Sensor

Pt1000

L

R3

R2

R1

GND

S1

S2

S3

S4

S5

VBus

PWM

1

PWM

2

N

R4

V40

L'

VFS

RPS

out

in

Note: 3-port valve normally open - tank 1 (S2)