The controller compares the temperature at sensor S1 to
the temperatures at sensors S2 and S4. If the measured
temperature differences are higher than the adjusted switch-
on temperature differences, the pump (R1) will be activated
and the corresponding tank zone will be loaded up to the

adjusted maximum temperature via the valve (R3). Tank 1
is loaded with priority. Heat exchange from tank 1 to tank
2 (R2) is possible with another temperature differential
function (S3-heat source/S4-heat sink).

Adjustment channels

Channel

Sub channel 1

Sub channel 2 Factory

setting

Change to

Description

Page

ARR

1

16

System

78

LOAD1 >

Loading 1

DT1O

12 °R

Switch-on temperature difference 1

78

DT1F

8 °R

Switch-off temperature difference 1

78

DT1S

20 °R

Set temperature difference 1

78

RIS1

4 °R

Rise 1

78

S1MAX

140 °F

Tank maximum limitation 1

78

SMXS1

2

Sensor tank max 1

79

LOAD2 >

Loading 2

DT2O

12 °R

Switch-on temperature difference 2

78

DT2F

8 °R

Switch-off temperature difference 2

78

DT2S

20 °R

Set temperature difference 2

78

RIS2

4 °R

rise 2

78

S2MAX

140 °F

Tank maximum limitation 2

78

SMXS2

4

Sensor tank max 2

79

LST2

ON

Loading tank 2

79

Sensor/Ter-
minal

Designation

Description

S1

TCOL

Temperature collector

S2

TST1B

Temperature tank 1 bottom

S3

TSTT

Temperature tank 1 top

S4

TST2B

Temperature tank 2 bottom

S5

Optional sensor for measurement
purposes or options

VFS
RPS
V40

Relay

Description

R1

Solar pump

R2

Heat exchange pump

R3

3-port valve tank 1 / 2

R4

optional:
Thermal disinfection
Parallel relay
Heat dump

System 16
2-tank solar system with valve logic and heat exchange control

R2

R3

R1

S4

S3

S2

S1

Temp. Sensor

Pt1000

L

R3

R2

R1

GND

S1

S2

S3

S4

S5

VBus

PWM

1

PWM

2

N

R4

V40

L'

VFS

RPS

out

in

Note: 3-port valve normally open
- tank 1 (S2)