The controller compares the temperatures at the collector
sensors S1 and S5 to the tank temperature at sensor S2. If
one of the measured temperature differences is higher than
the adjusted switch-on temperature differences, the corre-
sponding pump (R1, R2) or both pumps will be activated and

the tank will be loaded.
With another temperature differential function (S3-heat
source/S4-heat sink) heating circuit return preheating (he-
ating circuit backup) is possible with another valve (R3).

Adjustment channels

Channel

Sub channel 1

Sub channel 2 Factory

setting

Change to

Description

Page

ARR

1

21

System

78

LOAD >

Loading

DT O

12 °R

Switch-on temperature difference

78

DT F

8 °R

Switch-off temperature difference

78

DT S

20 °R

Set temperature difference

78

RIS

4 °R

Rise

78

S MAX

140 °F

Tank maximum limitation

78

SMAXS

2

Sensor tank max

79

COL 1 >

Collector 1

CEM1

270 °F

Collector emergency temperature 1

80

OCCO1**

OFF

Option collector cooling 1

80

CMAX1

230 °F

Maximum collector temperature 1

80

OCMI1

OFF

Option collector minimum limitation 1

80

CMIN1

50 °F

Minimum collector temperature 1

80

Sensor/Ter-
minal

Designation

Description

S1

TCOL1

Temperature collector 1

S2

TSTB

Temperature tank bottom

S3

TSTT

Temperature tank top

S4

TRET

Temperature - return

S5

TCOL2

Temperature collector 2

VFS

Optional sensor for measurement
purposes or options

RPS
V40

System 21
Solar system with east-/west collectors and heating circuit return preheating