In the adjustment channel n1(2, 3)LO, a relative minimum

speed for connected pumps can be allocated to the outputs

R1, R2 and R3.

Minimum speed

PUMP1 (2, 3) / n1 (2, 3 LO

Speed control
Adjustment range: 20 ... 100 %
in steps of 5%
Factory setting: 30 %

With this parameter, the pump control type can be adjusted.

The following types can be selected:
Adjustment for standard pump without speed control

• OnOF (pump on / pump off)
Adjustment for standard pump with speed control

• PULS (pulse packet control via semiconductor relay)
Adjustment for high efficiency pump (HE pump)

• PWM A (Wilo)
• PWM b (Grundfos)
• PWM C (Laing)

Pump control

PUMP / PUMP1 (2, 3,)

Pump control
Selection: OnOF, Puls, PWM A,
PWM b, PWM C,
Factory setting: OnOF

Sensor maximum tank temperature

Allocation of the sensor for tank maximum limitation. The
maximum limitation always refers to the sensor selected.
If S3 is selected, the differential control will be carried out
using S1 and S2. The temperature at S2 can exceed the
adjusted limit temperature, the system will not switch off.
If the value at S3 reaches the limit temperature, the system
will be switched off.

LOAD(1,2) / S(1,2)MAXS

Sensor tank maximum temp.
Adjustment range:
1-tank system: S2, S3
2-tank system: S4, S5
Factory setting:
1-tank system: S2
2-tank system: S4

note:
In 1-tank systems with sensor S3 as the reference

sensor, loading will be switched off if the tempe-

rature at S2 or S3 reaches the tank emergency

shutdown temperature.
In 2-tank systems, loading will be switched off

if the temperature at S4 or S5 reaches the tank

emergency shutdown temperature.

Loading tank 2

In a 2-tank system, the second tank can be switched off for

loading via the parameter LST2.
If LST2 is adjusted to OFF, the system runs like a 1-tank

system. The representation in the display does not change.

LOAD2 / LST2

Loading tank 2
Selection: ON / OFF
Factory setting: ON

note:
For more information about connecting HE

pumps, see page 68.

note:
When loads which are not speed-controlled (e. g.

valves) are used, the value of the corresponding

relay (n1, n2, n3) must be set to 100% or the

pump control type must be set to OnOF in

order to deactivate pump speed control.

note:
PUMP3 can only be set to OnOf or PULS.

note:
When loads which are not speed-controlled (e. g.

valves) are used, the value of the corresponding

relay (n1, n2, n3) must be set to 100% or the

pump control type must be set to OnOF in

order to deactivate pump speed control.

Maximum speed

PUMP1 (2, 3) / n1 (2, 3) HI

Speed control
Adjustment range: 20 ... 100 %
in steps of 5%
Factory setting: 100 %

In the adjustment channel n1(2, 3)HI, a relative maximum

speed for connected pumps can be allocated to the outputs

R1, R2 and R3.