Chapter 6 PLC Link

106

6

6.2.3 Setting the PLC

Set the PLC or link unit as follows:

Setting MELSEC-A series

1. Set the RS-232C communication parameters (baud rate, data length, parity and

stop bit length) according to the N-400’s settings.

2. Set the station number according to the N-400’s setting.

3. Set the mode to “Protocol Type 4 ”.

4. Set the main channel to “RS-232C”.

5. Set “Checksum” to “Enable”.

6. Set “Write during running” to “Enable”.

7. Set “Selecting computer link/multi-drop” to “Computer link” (for the AJ71UC24

only).

Setting SYSMAC-C series

1. Set the RS-232C communication parameters (baud rate, data length, parity and

stop bit length) according to the N-400’s settings.

2. Set the unit number according to the N-400’s setting.

3. Set the command level to “Level 1, 2, 3”.

4. Set “1:1/1:N” to “1:N”.

5. Set “I/O port” to “RS-232C”.

6. Set “Trigger input” to “Internal”.

7. Set “Supply 5 V” to “Disable”.

8. Set “CTS” to “0 V (Normally ON).”

*

The “I/O port”, “Trigger input”, “Supply 5 V” and “CTS” parameters may not be
provided depending on the type of link unit.

Setting KV series/handheld programmer port

1. The KV series’ handheld programmer port must always be set to the following

values:

• Baud rate : 9600 bps
• Data length: 8 bits
• Parity: Even
• Stop bit length: 1 bit

Set the RS-232C communication parameters of the N-400 according to the
above settings. Set the N-400’s communication mode to “KV”.

2. No other parameters need to be set.