Appendix D

Troubleshooting

If an abnormal condition occurs while operating this unit, check the following points.
If you cannot solve the problem, contact KEYENCE.

Communication is unsuccessful.

1) Check communication between the N-400 and each BL series using the N-

400’s connection test mode.
If communication is unsuccessful, check the following points:

1

Check if the power switches of the N-400 and all BL series are ON.

2

Check if the RS-485 communication parameters (baud rate, data length, parity
and stop bit length) for the BL series are the same as the N-400’s settings.

3

Check if the BL series is set to multi-drop link mode.

4

Check if the same ID number is assigned to different BL series.

5

Check if the specified cable is used for the multi-drop link connection, the cable
extension is within the specified distance (1.2 km), and the number of con-
nected BL series is within the specified range (thirty one).

6

Check if the multi-drop link connection is not passed through the terminal block
or not branched. (

See pp. 20 and 25.)

7

Check if the terminators are correctly set in the multi-drop link connection.
(

See pp. 20 and 25.)

2) Check the communication between the N-400 and the host computer for the

following points:

1

Check if the communication parameters (baud rate, data length, parity and stop
bit length) for the host computer are the same as the N-400’s settings.

2

Check if the N-400’s handshaking protocol is set as desired. Normally, the
handshaking protocol is set to “No handshaking”.